A closed damper think of it like the handle cutting off the flow of air.
Air conditioner damper open or closed.
Find the air conditioning duct trunks that lead out from the furnace.
An open damper the handle should be pointing down the duct.
Our photo shows a motorized zone damper or air duct zone control produced by trolatemp a producer of automatic heating system controls.
A damper is a valve or plate that stops or regulates the flow of air inside a duct chimney vav box air handler or other air handling equipment a damper may be used to cut off central air conditioning heating or cooling to an unused room or to regulate it for room by room temperature and climate control its operation can be manual or automatic.
If you have an hvac system with a fresh air intake set the system to recirculate mode or close the outdoor intake damper.
In modern systems the same fan in the furnace is used to move both heated and chilled air so any dampers are only to control the amount of airflow to different zones.
You don t say what this duct is to or why it would be open in one season or closed in another.
Manual dampers are turned by a handle on.
Reduce the smoke that enters your home.
One or more of the vents in the area should be still with minimal to no air flow.
Locate the damper lever on each duct.
Dampers use a door mechanism that opens to allow more air flow or closes to reduce air flow within a particular zone.
Also called the damper switch the vent in older windows and wall mounted ac units look like a tiny black knobs in the air inlet grill from where cold air is being blown into the room.
Open all the air conditioning vents or registers in the house so they are wide open.
The duct damper is located in an air duct and blocks the flow of warm or cool air into building rooms.
Each metal lever is located on the side of the duct.
Pulling on the damper opens the vent while pushing it in closes it.
If you cannot stay cool seek shelter elsewhere.
Open each damper by moving its lever so it points in the direction the duct travels not across it.
Use fans and air conditioning to stay cool.
Newer models will just have a button in place of the damper labeled as exhaust.
It has nothing to do with venting flue gases up a chimney.
If you have a window air conditioner close the outdoor.
Normally the horizontal position is open angled down about 70 80 degrees is closed.
Confirm the damper in question is yielding the result you want by opening it and closing it again just to be sure.
Keep windows and doors closed.